1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose — 50m Friction Loss Chart & Calculator
ID-measured 38 mm Australian CFA/RFS-style layflat firefighting delivery hose. Rated 1000 kPa working / 1200 kPa max with 38 mm true bore—delivers ~3x lower friction loss per metre than 1" fire hose at 150–250 L/min. Standard 38 mm Camlock, BIC, or Storz couplings.
- True Mean ID
- 38 mm
- Outside Dia (OD)
- 45 mm
- Wall Thickness
- 3.5 mm
- PN Rating (20°C)
- 1200 kPa 122 m max · 1000 kPa warn
- Derated (40°C)
- 1200 kPa Reinforced hose
- Safe Flow ≤1.5 m/s
- 102 L/min Hammer >163 L/min
- Fitting System
- Camlock, Storz, BIC or BSP Hose Tail
1 1/2" Fire Hose (38 mm) Friction Loss & Velocity Chart over 50 Metres
ID: 38 mm · ε = 0.005 mm · Hazen-Williams C = 140
| Flow (L/min) | Flow (L/hr) | Velocity (m/s) | Darcy Head (50m) | Darcy Drop (kPa) | Hazen-W C=140 (m) | Drop (PSI) | Safety Status |
|---|---|---|---|---|---|---|---|
| 10 | 600 | 0.15 | 0.05 m | 0.5 kPa | 0.05 m | 0.1 psi | Safe (≤1.5 m/s) |
| 20 | 1,200 | 0.29 | 0.18 m | 1.7 kPa | 0.17 m | 0.2 psi | Safe (≤1.5 m/s) |
| 40 | 2,400 | 0.59 | 0.59 m | 5.8 kPa | 0.61 m | 0.8 psi | Safe (≤1.5 m/s) |
| 60 | 3,600 | 0.88 | 1.21 m | 11.9 kPa | 1.30 m | 1.7 psi | Safe (≤1.5 m/s) |
| 80 | 4,800 | 1.18 | 2.03 m | 19.9 kPa | 2.21 m | 2.9 psi | Safe (≤1.5 m/s) |
| 100 | 6,000 | 1.47 | 3.03 m | 29.7 kPa | 3.34 m | 4.3 psi | Safe (≤1.5 m/s) |
| 120 | 7,200 | 1.76 | 4.20 m | 41.2 kPa | 4.69 m | 6.0 psi | Caution (1.5–2.4 m/s) |
| 140 | 8,400 | 2.06 | 5.55 m | 54.5 kPa | 6.24 m | 7.9 psi | Caution (1.5–2.4 m/s) |
| 160 | 9,600 | 2.35 | 7.08 m | 69.4 kPa | 7.99 m | 10.1 psi | Caution (1.5–2.4 m/s) |
| 180 | 10,800 | 2.65 | 8.76 m | 85.9 kPa | 9.93 m | 12.5 psi | Water Hammer (>2.4 m/s) |
| 200 | 12,000 | 2.94 | 10.62 m | 104.1 kPa | 12.08 m | 15.1 psi | Water Hammer (>2.4 m/s) |
Notes: Friction figures represent straight-pipe major losses only (20°C clean water, Colebrook-White Darcy-Weisbach). Add static elevation, suction lift, outlet pressure, and minor fitting losses (barbed elbows/joiners, foot valve, check valves) using the live calculator below.
Step up to 2" Suction/Delivery Hose & cut friction by 73.2%
Stepping up from 1 1/2" Fire Hose (38 mm) (38 mm ID) to 2" Suction/Delivery Hose (50 mm ID) cuts pipe friction by 73.2% (saving 1.5 m / 15 kPa) and lowers velocity from 1.18 to 0.68 m/s.
High-flow delivery & coupling discipline for 1 1/2" Fire Hose (38 mm)
1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose carries a 38 mm true bore with wall roughness ε = 0.005 mm (Hazen-Williams C = 140). Keep delivery hoses unkinked and ensure suction lines never exceed 5.5 m combined static lift + foot-valve friction.
1 1/2" Fire Hose (38 mm) vs Next Size Up (2" Suction/Delivery Hose) — 50 m Run
Length: 50 m · Static Rise: 10 m · Outlet: 100 kPa · Darcy-Weisbach (20°C)
Interactive 1 1/2" Fire Hose (38 mm) (50m) Pump & Friction Solver
Pre-loaded with 50 m of 1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose (38 mm ID) at 80 L/min. Adjust elevation, fittings, water temperature, and pump archetype below.
1. Pipe Standard & Size
44 AU SpecsID-measured 38 mm Australian CFA/RFS-style layflat firefighting delivery hose. Rated 1000 kPa working / 1200 kPa max with 38 mm true bore—delivers ~3x lower friction loss per metre than 1" fire hose at 150–250 L/min. Standard 38 mm Camlock, BIC, or Storz couplings.
2. Site Run & Hydraulic Conditions
Equivalent: 4,800 L/hr · 115,200 L/24h
3. Fittings & Valves (2)
ΣK = 4.65 · +7.9 m eq. pipe · 0.33 m loss
Suction Intake & Strainer
Directly increases pump suction head — critical for the 5.5 m cavitation & priming guardrail.
Highest single fitting loss in typical farm systems due to strainer mesh + hinged/poppet check flap on the suction side—critical for cavitation & 5.5 m suction lift checks! Oversizing suction line by one size cuts this penalty dramatically.
Loss: 0.32 m (3.1 kPa · +7.6 m eq.)
Delivery Fittings & Non-Return Valves
Note the steep minor-loss penalty of internal rural barbed inserts vs. full-bore external metric compression fittings.
Internal insert barb steps down inside the pipe wall (reducing local ID by ~4–6 mm), creating sudden contraction/expansion turbulence—nearly 5x the loss of an external metric compression joiner.
High minor loss caused by the dual restriction of an internal barbed spigot combined with an abrupt short-radius 90° direction change. Use sweeping pipe bends instead wherever trench layout allows.
Severe bore restriction from internal insert barbs plus 90° dividing/combining branch turbulence. Multiple barbed tees in series rapidly erode available pump head.
Full-bore external O-ring and split-ring grip seal—zero internal barb intrusion, keeping velocity profile smooth and minor loss minimal.
External compression body preserves full internal bore diameter through the 90° turn, cutting head loss by more than half versus a rural barbed elbow.
Full-bore external seal eliminates barb necking, leaving only the 90° branch turning loss (~half the K-factor of a barbed rural tee).
Lower head loss than spring-loaded check valves once flow lifts the flap fully open, but slower closure can trigger water-hammer slam on steep rising mains.
Higher resistance due to spring tension and poppet obstruction around the seat, but rapid non-slam closure prevents reverse-flow water hammer on steep hills and bore risers.
Isolation Valves
Low friction when fully open; avoid snapping quarter-turn ball valves shut on lines above 1.5 m/s.
True full-port ball bore aligns cleanly with pipe ID when open (negligible loss). Warning: never snap quarter-turn valves shut rapidly on high-velocity lines (>1.5 m/s) or severe water hammer will spike pipe pressure.
Loss: 0.01 m (0.1 kPa · +0.3 m eq.)
Gate retracts completely clear of the flow path when fully open, giving minimal friction loss. Slow multi-turn closure naturally protects PE poly mains against sudden water-hammer spikes.
Water velocity is 1.18 m/s, safely within the <= 1.5 m/s design range for low friction and minimal water hammer.
Total dynamic pressure (236 kPa) is safely within 1 1/2" Fire Hose (38 mm) working rating (1000 kPa warning / 1200 kPa max).
Total suction head is 1.82 m, safely below the 5.5 m cavitation & priming threshold.
Interactive System Curve vs. Australian Pump Curves
Click any pump chip below to overlay its H-Q curve, check shut-off pressure against pipe PN rating, and locate the exact duty point.
No Direct Rural-vs-Metric Naming Trap
1 1/2" Fire Hose (38 mm) (38 mm true ID) does not share an ambiguous Rural/Metric nominal pair. Standard rural Class B poly tops out at 2" (50.9 mm ID), whereas DN63–DN90 Metric PE100 pipes offer larger high-pressure bores.
Step Up to 2" Suction/Delivery Hose
Stepping up from 1 1/2" Fire Hose (38 mm) (38 mm ID) to 2" Suction/Delivery Hose (50 mm ID) cuts pipe friction by 73.2% (saving 1.5 m / 15 kPa) and lowers velocity from 1.18 to 0.68 m/s.
Recommended Australian Pump Archetypes (Ranked for Your System)
Exact bisection intersection between each pump's H-Q curve and your 50 m 1 1/2" Fire Hose (38 mm) system curve. Click any pump to inspect on the chart and verify dead-head pipe safety.
| Pump Archetype | Power | Solved Operating Duty Point | Shut-Off Head | Status | Est. AU Price | Compare |
|---|---|---|---|---|---|---|
2" Trash / Transfer PumpActive Strong match: delivers 118.4 L/min at 26.5 m head (1.74 m/s) safely within pipe pressure limits. | Petrol | 118.4 L/min @ 26.5 m 260 kPa · 1.74 m/s | 28 m (275 kPa) | Recommended Match | $450–$980 AUD | |
240V Multistage Irrigation Pump Strong match: delivers 137.5 L/min at 28.0 m head (2.02 m/s) safely within pipe pressure limits. | 240V AC | 137.5 L/min @ 28.0 m 275 kPa · 2.02 m/s | 62 m (608 kPa) | Recommended Match | $650–$1,450 AUD | |
Single-Impeller Fire Pump Meets target flow at 265.6 L/min (43.2 m head), but note: high velocity (3.90 m/s), oversized for target flow. | Petrol | 265.6 L/min @ 43.2 m 423 kPa · 3.90 m/s | 70 m (686 kPa) | Capable (Check Sizing) | $550–$1,150 AUD | |
Twin-Impeller Fire Pump Meets target flow at 277.5 L/min (45.0 m head), but note: high velocity (4.08 m/s), oversized for target flow. | Petrol | 277.5 L/min @ 45.0 m 441 kPa · 4.08 m/s | 98 m (961 kPa) | Capable (Check Sizing) | $850–$1,650 AUD | |
240V Tank Jet Pump Delivers 58.0 L/min (72% of 80 L/min target) at 23.0 m head. | 240V AC | 58.0 L/min @ 23.0 m 226 kPa · 0.85 m/s | 46 m (451 kPa) | Undersized Flow | $380–$780 AUD | |
Solar Bore Pump (24V/48V) Delivers 54.5 L/min (68% of 80 L/min target) at 22.9 m head. | Solar DC | 54.5 L/min @ 22.9 m 224 kPa · 0.80 m/s | 75 m (735 kPa) | Undersized Flow | $1,400–$3,200 AUD |
Bill of Materials (BOM) & Printable Engineering Spec Sheet
Standard Australian poly coil rollup, fitting-system compatibility guard, and counted hardware ready to hand to your rural supply branch.
+ 1 straight coil-to-coil joiner recommended to connect rolls.
Use 1 1/2" (38 mm ID) Australian Camlock, Storz, BIC, or BSP hose-tail couplings secured with heavy-duty T-bolt or Band-It clamps.
- 1 × 2" High-Flow Petrol Trash & Dam Transfer Pump$450–$980 AUDInlet 50 mm / Outlet 50 mm · Shut-off 28 m
- 1 × Suction Foot Valve & Strainer BasketK=4.50 · 0.32 m
- 1 × Full-Bore Quarter-Turn Ball Valve (Fully Open)K=0.15 · 0.01 m
Source Matched Pipe, Fittings & Pumps for This Spec
Links adapt dynamically to your chosen pipe family (1 1/2" Fire Hose (38 mm)) and active pump category (2" Trash / Transfer Pump).
Australian Petrol Firefighting & Bulk Transfer Pumps
GX-style single-impeller, twin-impeller high-head, and 2" trash transfer pumps ready for rural delivery.
Heavy-Duty Suction Hose, Fire Reels & Non-Return Foot Valves
Vacuum-rated 2" helical suction kits and 1"–1.5" layflat hoses with Australian Camlock and Storz fittings.
AusFlowSpec is independently built for Australian rural water engineering. Some supplier links below are affiliate or quote-referral partners—if you buy or request a quote through them, we may earn a small commission at zero extra cost to you. Engineering calculations are never influenced by partner placement.
Engineering Q&A: 1 1/2" Fire Hose (38 mm) over 50 Metres
What is the maximum safe flow rate for 1 1/2" Fire Hose (38 mm) (38 mm ID)?
For continuous farm and irrigation service at or below the 1.5 m/s velocity guideline, 1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose (38 mm true internal diameter) safely carries up to 102.1 L/min (6,124 L/hr). Above 163.3 L/min (2.4 m/s), flow enters the water-hammer risk zone where rapid valve closure can spike pressure sharply.
How much friction head loss does 50m of 1 1/2" Fire Hose (38 mm) have at 80 L/min?
Over a 50 m run at 80 L/min (velocity 1.18 m/s, 20°C water), 1 1/2" Fire Hose (38 mm) loses 2.03 m of head (20 kPa / 2.9 PSI) via Darcy-Weisbach, compared with 2.21 m using Hazen-Williams (C=140).
What is the maximum pressure rating of 1 1/2" Fire Hose (38 mm) in hot Australian summer conditions?
1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose is rated to 1000 kPa continuous working pressure and 1200 kPa maximum (122.4 m head) using reinforced hose construction (not PE temperature-derated under AS/NZS 4130, though always inspect couplings and avoid kinks).
How much friction does stepping up from 1 1/2" Fire Hose (38 mm) to 2" Suction/Delivery Hose save over 50m?
At 80 L/min over 50 m, stepping up from 1 1/2" Fire Hose (38 mm) (38 mm ID) to 2" Suction/Delivery Hose (50 mm ID) cuts pipe friction loss by 73.2%—saving 1.49 m of head (15 kPa) and reducing water velocity from 1.18 m/s down to 0.68 m/s.