1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose — 100m Friction Loss Chart & Calculator

ID-measured 38 mm Australian CFA/RFS-style layflat firefighting delivery hose. Rated 1000 kPa working / 1200 kPa max with 38 mm true bore—delivers ~3x lower friction loss per metre than 1" fire hose at 150–250 L/min. Standard 38 mm Camlock, BIC, or Storz couplings.

Switch Run Length (1 1/2" Fire Hose (38 mm))
True Mean ID
38 mm
Outside Dia (OD)
45 mm
Wall Thickness
3.5 mm
PN Rating (20°C)
1200 kPa 122 m max · 1000 kPa warn
Derated (40°C)
1200 kPa Reinforced hose
Safe Flow ≤1.5 m/s
102 L/min Hammer >163 L/min
Fitting System
Camlock, Storz, BIC or BSP Hose Tail
Zero-JS Engineering Reference Table · 20°C Water

1 1/2" Fire Hose (38 mm) Friction Loss & Velocity Chart over 100 Metres

ID: 38 mm · ε = 0.005 mm · Hazen-Williams C = 140

Flow (L/min) Flow (L/hr) Velocity (m/s) Darcy Head (100m) Darcy Drop (kPa) Hazen-W C=140 (m) Drop (PSI) Safety Status
10 600 0.15 0.11 m 1.0 kPa 0.09 m 0.2 psi Safe (≤1.5 m/s)
20 1,200 0.29 0.35 m 3.4 kPa 0.34 m 0.5 psi Safe (≤1.5 m/s)
40 2,400 0.59 1.18 m 11.6 kPa 1.23 m 1.7 psi Safe (≤1.5 m/s)
60 3,600 0.88 2.43 m 23.8 kPa 2.60 m 3.5 psi Safe (≤1.5 m/s)
80 4,800 1.18 4.06 m 39.8 kPa 4.43 m 5.8 psi Safe (≤1.5 m/s)
100 6,000 1.47 6.06 m 59.4 kPa 6.69 m 8.6 psi Safe (≤1.5 m/s)
120 7,200 1.76 8.41 m 82.5 kPa 9.38 m 12.0 psi Caution (1.5–2.4 m/s)
140 8,400 2.06 11.11 m 108.9 kPa 12.48 m 15.8 psi Caution (1.5–2.4 m/s)
160 9,600 2.35 14.15 m 138.8 kPa 15.98 m 20.1 psi Caution (1.5–2.4 m/s)
180 10,800 2.65 17.53 m 171.9 kPa 19.87 m 24.9 psi Water Hammer (>2.4 m/s)
200 12,000 2.94 21.23 m 208.2 kPa 24.15 m 30.2 psi Water Hammer (>2.4 m/s)

Notes: Friction figures represent straight-pipe major losses only (20°C clean water, Colebrook-White Darcy-Weisbach). Add static elevation, suction lift, outlet pressure, and minor fitting losses (barbed elbows/joiners, foot valve, check valves) using the live calculator below.

Fire & Suction HosePVC/Layflat Suction & Delivery · ID-Measured

Interactive 1 1/2" Fire Hose (38 mm) (100m) Pump & Friction Solver

Pre-loaded with 100 m of 1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose (38 mm ID) at 80 L/min. Adjust elevation, fittings, water temperature, and pump archetype below.

1. Pipe Standard & Size

44 AU Specs
Measured By
ID (Bore)
True Bore ID
38 mm
Outside OD
45 mm
Max @ 20°C
1200 kPa

ID-measured 38 mm Australian CFA/RFS-style layflat firefighting delivery hose. Rated 1000 kPa working / 1200 kPa max with 38 mm true bore—delivers ~3x lower friction loss per metre than 1" fire hose at 150–250 L/min. Standard 38 mm Camlock, BIC, or Storz couplings.

2. Site Run & Hydraulic Conditions

L/min

Equivalent: 4,800 L/hr · 115,200 L/24h

3 × 30 m coils + 1 × 20 m coil
m
+98 kPa uphill
m
Total Suction: 1.82 m / 5.5 m max
m
m
KPA
100% nominal PN rating (≤ 20°C)
°C

3. Fittings & Valves (2)

ΣK = 4.65 · +7.9 m eq. pipe · 0.33 m loss

Suction Intake & Strainer

Directly increases pump suction head — critical for the 5.5 m cavitation & priming guardrail.

Foot Valve & StrainerK=4.5 · 200DHigh suction loss

Highest single fitting loss in typical farm systems due to strainer mesh + hinged/poppet check flap on the suction side—critical for cavitation & 5.5 m suction lift checks! Oversizing suction line by one size cuts this penalty dramatically.

Loss: 0.32 m (3.1 kPa · +7.6 m eq.)

1

Delivery Fittings & Non-Return Valves

Note the steep minor-loss penalty of internal rural barbed inserts vs. full-bore external metric compression fittings.

Rural Barbed JoinerK=1.2 · 55DDifferent fitting systemInternal barb restriction

Internal insert barb steps down inside the pipe wall (reducing local ID by ~4–6 mm), creating sudden contraction/expansion turbulence—nearly 5x the loss of an external metric compression joiner.

0
Rural Barbed 90° ElbowK=1.9 · 85DDifferent fitting systemInternal barb restriction

High minor loss caused by the dual restriction of an internal barbed spigot combined with an abrupt short-radius 90° direction change. Use sweeping pipe bends instead wherever trench layout allows.

0
Rural Barbed Tee (Branch)K=2.4 · 110DDifferent fitting systemInternal barb restriction

Severe bore restriction from internal insert barbs plus 90° dividing/combining branch turbulence. Multiple barbed tees in series rapidly erode available pump head.

0
Metric Compression JoinerK=0.25 · 12DDifferent fitting system

Full-bore external O-ring and split-ring grip seal—zero internal barb intrusion, keeping velocity profile smooth and minor loss minimal.

0
Metric Compression 90° ElbowK=0.75 · 32DDifferent fitting system

External compression body preserves full internal bore diameter through the 90° turn, cutting head loss by more than half versus a rural barbed elbow.

0
Metric Compression Tee (Branch)K=1.2 · 55DDifferent fitting system

Full-bore external seal eliminates barb necking, leaving only the 90° branch turning loss (~half the K-factor of a barbed rural tee).

0
Swing Check ValveK=2 · 90D

Lower head loss than spring-loaded check valves once flow lifts the flap fully open, but slower closure can trigger water-hammer slam on steep rising mains.

0
Spring Check ValveK=3.2 · 140D

Higher resistance due to spring tension and poppet obstruction around the seat, but rapid non-slam closure prevents reverse-flow water hammer on steep hills and bore risers.

0

Isolation Valves

Low friction when fully open; avoid snapping quarter-turn ball valves shut on lines above 1.5 m/s.

Full-Bore Ball ValveK=0.15 · 8D

True full-port ball bore aligns cleanly with pipe ID when open (negligible loss). Warning: never snap quarter-turn valves shut rapidly on high-velocity lines (>1.5 m/s) or severe water hammer will spike pipe pressure.

Loss: 0.01 m (0.1 kPa · +0.3 m eq.)

1
Gate Valve (Open)K=0.2 · 10D

Gate retracts completely clear of the flow path when fully open, giving minimal friction loss. Slow multi-turn closure naturally protects PE poly mains against sudden water-hammer spikes.

0
Australian Supply Match

Source Matched Pipe, Fittings & Pumps for This Spec

Links adapt dynamically to your chosen pipe family (1 1/2" Fire Hose (38 mm)) and active pump category (2" Trash / Transfer Pump).

AU Fire & TransferAU Supplier

Australian Petrol Firefighting & Bulk Transfer Pumps

GX-style single-impeller, twin-impeller high-head, and 2" trash transfer pumps ready for rural delivery.

View Matching 2" Trash Transfer Pumps
Fire & Suction HoseAU Supplier

Heavy-Duty Suction Hose, Fire Reels & Non-Return Foot Valves

Vacuum-rated 2" helical suction kits and 1"–1.5" layflat hoses with Australian Camlock and Storz fittings.

Price 110m of 1 1/2" Fire Hose (38 mm) + Camlock Kits

AusFlowSpec is independently built for Australian rural water engineering. Some supplier links below are affiliate or quote-referral partners—if you buy or request a quote through them, we may earn a small commission at zero extra cost to you. Engineering calculations are never influenced by partner placement.

Engineering Q&A: 1 1/2" Fire Hose (38 mm) over 100 Metres

What is the maximum safe flow rate for 1 1/2" Fire Hose (38 mm) (38 mm ID)?

For continuous farm and irrigation service at or below the 1.5 m/s velocity guideline, 1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose (38 mm true internal diameter) safely carries up to 102.1 L/min (6,124 L/hr). Above 163.3 L/min (2.4 m/s), flow enters the water-hammer risk zone where rapid valve closure can spike pressure sharply.

How much friction head loss does 100m of 1 1/2" Fire Hose (38 mm) have at 80 L/min?

Over a 100 m run at 80 L/min (velocity 1.18 m/s, 20°C water), 1 1/2" Fire Hose (38 mm) loses 4.06 m of head (40 kPa / 5.8 PSI) via Darcy-Weisbach, compared with 4.43 m using Hazen-Williams (C=140).

What is the maximum pressure rating of 1 1/2" Fire Hose (38 mm) in hot Australian summer conditions?

1 1/2" (38 mm) Australian Firefighting Layflat Delivery Hose is rated to 1000 kPa continuous working pressure and 1200 kPa maximum (122.4 m head) using reinforced hose construction (not PE temperature-derated under AS/NZS 4130, though always inspect couplings and avoid kinks).

How much friction does stepping up from 1 1/2" Fire Hose (38 mm) to 2" Suction/Delivery Hose save over 100m?

At 80 L/min over 100 m, stepping up from 1 1/2" Fire Hose (38 mm) (38 mm ID) to 2" Suction/Delivery Hose (50 mm ID) cuts pipe friction loss by 73.2%—saving 2.97 m of head (29 kPa) and reducing water velocity from 1.18 m/s down to 0.68 m/s.